Signal converter for electromagnetic flowmetersElectronic Revision:ER 3.3.xx(SW.REV. 3.3x)IFC 300IFC 300IFC 300IFC 300Quick Start Quick Start Quick St
2 INSTALLATION 10 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en2.7.4 Turning the display of the field housing versionThe display of
INSTALLATION 211IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en2.8 Mounting the wall-mounted housing, remote version2.8.1 Pipe mounti
2 INSTALLATION 12 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en2.8.2 Wall mounting1 Prepare the holes with the aid of the mounting
INSTALLATION 213IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en2.8.3 Mounting plate, wall-mounted housingDimensions in mm and inch[mm]
3 ELECTRICAL CONNECTIONS 14 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.1 Safety instructions3.2 Important notes on electrical c
ELECTRICAL CONNECTIONS 315IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.3 Electrical cables for remote device versions, notes3.3.1
3 ELECTRICAL CONNECTIONS 16 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.3.3 Requirements for signal cables provided by the custom
ELECTRICAL CONNECTIONS 317IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.4 Preparing the signal and field current cables (except TID
3 ELECTRICAL CONNECTIONS 18 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.4.2 Preparing signal cable A, connection to signal conver
ELECTRICAL CONNECTIONS 319IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 enWall mounted housing• The connection of the outer shield (60)
CONTENTS 2 www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enIFC 3001 Safety instructions 42 Installation 52.1 Intended use ...
3 ELECTRICAL CONNECTIONS 20 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.4.3 Length of signal cable AINFORMATION!For temperatures
ELECTRICAL CONNECTIONS 321IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.4.4 Signal cable B (type BTS 300), construction• Signal cab
3 ELECTRICAL CONNECTIONS 22 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en1 Strip the conductor to dimension a. 2 Trim the outer shi
ELECTRICAL CONNECTIONS 323IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 enWall-mounted housing• The connection of the outer shield (60)
3 ELECTRICAL CONNECTIONS 24 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.4.6 Length of signal cable BINFORMATION!For temperatures
ELECTRICAL CONNECTIONS 325IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.4.7 Preparing field current cable C, connection to signal c
3 ELECTRICAL CONNECTIONS 26 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enIn the wall-mounted housing version the connection terminals
ELECTRICAL CONNECTIONS 327IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.4.8 Preparing signal cable A, connection to measuring senso
3 ELECTRICAL CONNECTIONS 28 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.4.9 Preparing signal cable B, connection to measuring sen
ELECTRICAL CONNECTIONS 329IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.4.10 Preparing field current cable C, connection to measuri
CONTENTS 3www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 enIFC 3003.6 Preparing and connecting the signal and field current cables (only TIDAL
3 ELECTRICAL CONNECTIONS 30 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.5 Connecting the signal and field current cables (except
ELECTRICAL CONNECTIONS 331IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.5.1 Connecting the signal and field current cables, field h
3 ELECTRICAL CONNECTIONS 32 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.5.2 Connecting the signal and field current cables, wall-
ELECTRICAL CONNECTIONS 333IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.5.3 Connecting the signal and field current cables, 19"
3 ELECTRICAL CONNECTIONS 34 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.5.4 Connecting the signal and field current cables, 19&qu
ELECTRICAL CONNECTIONS 335IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.5.5 Connection diagram for measuring sensor, field housing•
3 ELECTRICAL CONNECTIONS 36 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.5.6 Connection diagram for measuring sensor, wall-mounted
ELECTRICAL CONNECTIONS 337IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.5.7 Connection diagram for measuring sensor, 19" rack-
3 ELECTRICAL CONNECTIONS 38 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.5.8 Connection diagram for measuring sensor, 19" rac
ELECTRICAL CONNECTIONS 339IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6 Preparing and connecting the signal and field current cab
1 SAFETY INSTRUCTIONS 4 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enWarnings and symbols usedHANDLING• This symbol designates all i
3 ELECTRICAL CONNECTIONS 40 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.6.2 Signal cable A (type DS 300), construction• Signal ca
ELECTRICAL CONNECTIONS 341IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6.3 Preparing signal cable A, connection to signal converte
3 ELECTRICAL CONNECTIONS 42 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.6.4 Prepare signal cable A, connect to measuring sensorRe
ELECTRICAL CONNECTIONS 343IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6.5 Signal cable B (type BTS 300), construction• Signal cab
3 ELECTRICAL CONNECTIONS 44 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en1 Strip the conductor to dimension a. 2 Trim the outer shi
ELECTRICAL CONNECTIONS 345IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6.7 Preparing signal cable B, connection to measuring senso
3 ELECTRICAL CONNECTIONS 46 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.6.8 Preparing field current cable C, connection to signal
ELECTRICAL CONNECTIONS 347IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6.9 Preparing field current cable C, connection to measurin
3 ELECTRICAL CONNECTIONS 48 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enAt flow converter side:At flow sensor side:Connecting shield
ELECTRICAL CONNECTIONS 349IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.6.10 Interface cableThe data interface cable is a shielded,
INSTALLATION 25IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en2.1 Intended useThe electromagnetic flowmeters are designed exclusively
3 ELECTRICAL CONNECTIONS 50 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.6.11 Connection of cablesFigure 3-35: Electrical connecti
ELECTRICAL CONNECTIONS 351IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 enFlow sensors with protection class IP 68 can not be opened any
3 ELECTRICAL CONNECTIONS 52 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.7.2 Virtual reference (not valid for TIDALFLUX 4000 &
ELECTRICAL CONNECTIONS 353IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en100...230 VAC (tolerance range: -15% / +10%)100...230 VAC (tol
3 ELECTRICAL CONNECTIONS 54 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enPower supply connection (excluding 19" rack-mounted hou
ELECTRICAL CONNECTIONS 355IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.9 Inputs and outputs, overview3.9.1 Combinations of the in
3 ELECTRICAL CONNECTIONS 56 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.9.2 Description of the CG numberThe last 3 digits of the
ELECTRICAL CONNECTIONS 357IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.9.3 Fixed, non-alterable input/output versionsThis signal c
3 ELECTRICAL CONNECTIONS 58 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enCG no. Connection terminalsA+ A A- B B- C C- D D-PROFIBUS PA
ELECTRICAL CONNECTIONS 359IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.9.4 Alterable input/output versionsThis signal converter is
2 INSTALLATION 6 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 enPossible scope of delivery for signal converter / measuring sensor2.3
3 ELECTRICAL CONNECTIONS 60 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.10 Electrical connection of the inputs and outputs3.10.1
ELECTRICAL CONNECTIONS 361IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.10.2 Wall-mounted housing, electrical connection of the inp
3 ELECTRICAL CONNECTIONS 62 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en3.10.3 19" rack-mounted housing (28 TE), electrical co
ELECTRICAL CONNECTIONS 363IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en3.10.4 19" rack-mounted housing (21 TE), electrical conn
4 START-UP 64 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en4.1 Switching on the powerBefore connecting to power, please check that t
NOTES 565IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en
5 NOTES 66 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en
NOTES 567IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en
KROHNE product overview• Electromagnetic flowmeters• Variable area flowmeters• Ultrasonic flowmeters• Mass flowmeters• Vortex flowmeters• Flow control
INSTALLATION 27IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en2.6 Mounting of the compact version2.7 Mounting the field housing, remo
2 INSTALLATION 8 IFC 300www.krohne.com 08/2010 - 4000070303 - QS IFC 300 R06 en2.7.2 Wall mounting1 Prepare the holes with the aid of the mounting p
INSTALLATION 29IFC 300www.krohne.com08/2010 - 4000070303 - QS IFC 300 R06 en2.7.3 Mounting plate, field housingDimensions in mm and inch[mm] [inch]a
Comments to this Manuals