1 General Information 3 1.1 Point-to-Point Analog/Digital Mode 3 1.2 Multidrop Mode 4 1.3 Multidrop Mode (‘three-wire’) 5 2 IDs and Revision
1 General Information The M8E is a two-wire transmitter with 4...20mA current output and HART capability. General Characteristics of the M8E HART
Multidrop Mode b) As a multipoint connection (multidrop) with up to 15 devices (M8E or other HART equipment) in parallel. Multidrop ModePower Sup
1.3 Multidrop Mode (‘three-wire’) In case devices with current output shall work continuously active a 'third wire' is needed to properly
3 Implementation Peculiarities Transmitter • All parameters and dynamic data are involved in HART transactions, i.e. can be handled from remote hos
5 Asset Management Solutions (AMS) 5.1 Installation If the M8E Device Description is not already installed on the AMS System a so called Installati
Attachment A 1 Process Variables 2 Analog Output 3 Test/Info 4 Installation 5 Quit/Reset 6 HART Vari
Attachment B M8E Menu Tree AMS • Flow • Flow, scaled by URV/LRV • Flow, scaled by USL/LSL • Po