Operating InstructionsOPTISWITCH 3000 Cwith two-wire output
Warning:The housing must not be used to screw in the instrument!Applying tightening force on the housing can damage itsinternal mechanical parts.To sc
To achieve a very precise switching point, you can installOPTISWITCH 3000 C horizontally. However, if the switchingpoint can have a tolerance of a few
21Fig. 5: Orientation of the tuning fork in case of flow1 Marking with screwed version2 Direction of flowIn case of horizontal mounting in adhesive prod
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
10 Screw the housing cover back onThe electrical connection is hence finished.Fig. 7: Connection steps 5 and 65.3 Wiring plan, single chamber housing41
For connection to a signal conditioning instrument. The sensoris powered via the connected signal conditioning instrument.For further information see
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.On the electronics module you will find the following indicatingand adj
6.2 Adjustment elements4123Fig. 10: Electronics module - Two-wire output1 DIL switch for mode adjustment2 Ground terminal3 Screwed terminals4 Control
6.3 Function chartOPTISWITCH 3000 C level switchThe following chart provides an overview of the switchingconditions depending on the adjusted mode and
Mode on the signalconditioning instru-mentLevel Signal current -SensorSignal lamp - sensor Signal lamp - sig-nal conditioninginstrumentMode AOverfill p
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH3000 C is completely maintenance free.7.2 Rect
l Wrong mode selectedà Set the mode switch on OPTISWITCH 3000 C to"max". Set the correct mode on the signal conditioninginstrument (A: overfi
8 Compare the settings of the two oscillators. Set theadjustment elements of the new oscillator to the samesetting of the old one.Information:Make sur
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread plastic PBT (P
Process conditionsParameter Limit level of solidsProcess pressure -1 … 6 bar/-100 … 600 kPa (-14.5 … 87 psi)Process temperature -50 … +100 °C (-58 … +
9.2 DimensionsOPTISWITCH 3000 C22mm(55/64")30,4mm(1 13/64")G1½A150mm (5 29/32")220,5mm (8 11/16")ø 43mm (1 11/16")Fig. 12: OP
9.3 CertificatesCE declarations of conformityFig. 13: CE declarations of conformityOPTISWITCH 3000 C - with two-wire output 27Supplement30061-EN-060830
Manufacturer declarationFig. 14: Manufacturer declarationSupplement28 OPTISWITCH 3000 C - with two-wire output30061-EN-060830
SupplementOPTISWITCH 3000 C - with two-wire output 2930061-EN-060830
9.2 Dimensions ...269.3 Certificates ...27Supplementary operating instructions manualsInformation:OPTIS
Supplement30 OPTISWITCH 3000 C - with two-wire output30061-EN-060830
SupplementOPTISWITCH 3000 C - with two-wire output 3130061-EN-060830
Subject to change without notice30061-EN-060830
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 3000 C level sensorl Documentation- this operating instructions ma
Fault monitoringThe electronics of OPTISWITCH 3000 C continuously mon-itors the following criteria:l Correct vibrating frequencyl Line break to the pi
l Storage and transport temperature see "Supplement -Technical data - Ambient conditions"l Relative humidity 20 … 85 %Storage and transport
4 Mounting4.1 General instructionsIn general, OPTISWITCH 3000 C can be mounted in anyposition. The instrument must be mounted in such a way thatthe vi