Safety Manual
OPTISWITCH series 3000
- NAMUR
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - Safety Manual

Safety ManualOPTISWITCH series 3000- NAMUR

Page 2

Overflow protection(max. operation)Dry run protection(min. operation)λsd12 FIT 36 FITλsu160 FIT 155 FITλdd390 FIT 366 FITλdu47 FIT 52 FITDCS7 % 19 %DCD

Page 3 - 1 Functional safety

1 5 10TProof PFDavg1234Fig. 1: Chronological sequence of PFDavg(figures see above charts)1 PFDavg= 02 PFDavgafter 1 year3 PFDavgafter 5 years4 PFDavgaf

Page 4 - 1.2 Planning

Subject to change without notice32742-EN-080414

Page 5

Content1 Functional safety1.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31.2 Planning . . . . . . . . . . . . . . . . . . . .

Page 6

1 Functional safety1.1 GeneralThis safety manual applies to measuring systems consisting ofthe vibrating level switch OPTISWITCH series 3000 withinteg

Page 7 - 1.4 Setup

FIT Failure In Time (1 FIT = 1 failure/109h)MTBF Mean Time Between FailureMTTF Mean Time To FailureMTTR Mean Time To Repairl IEC 61508 (also available

Page 8 - 1.6 Recurring function test

The safe state depends on the mode:Overflow protection(max. operation)Dry run protection(min. operation)Vibrating element in safestatecovered uncovered

Page 9

If the ratio of the internal diagnostics test rate of the measuringsystem to the demand rate exceeds the value 100, themeasuring system can be treated

Page 10 - 32742-EN-080414

The measuring system should be used appropriately takingpressure, temperature, density and chemical properties of themedium into account.The user-spec

Page 11

An exchange of the electronics is easily possible and isdescribed in the operating instructions manual.If due to a detected failure the electronics or

Page 12

This function test is triggered by an interruption of the supplycable for at least two seconds. Then a special warm-upreaction of the current output i