10 Installation and operating instructions BM 100 A Process connection and entry pipe Caution: Do not put the nozzle close to the entry
Installation and operating instructions BM 100 A 11 1.3.3 Installation instructions: Gauge - all applications BM100 A gauges are designed
12 Installation and operating instructions BM 100 A Cable probes: entanglement and straightness The cable must be straight once inserted
Installation and operating instructions BM 100 A 13 1 Turnbuckle 2 Chuck for type H Ø4 single cable probe 3 Counterweight with threaded
14 Installation and operating instructions BM 100 A Traction forces during emptying cycles for powder applications Traction load is depen
Installation and operating instructions BM 100 A 15 2 Electrical Connections 2.1 Insulation rating The gauge transmitter electrical insula
16 Installation and operating instructions BM 100 A 2.2 Electrical installation instructions 2.2.1 Wiring general notes Read thes
Installation and operating instructions BM 100 A 17 2.2.2 Wiring connections Open the signal converter housing rear cover, using the plas
18 Installation and operating instructions BM 100 A Terminal layout: Ex version (X) = Terminal not used except for RS
Installation and operating instructions BM 100 A 19 Options, output The output wires should be wired to the gauge terminals according to t
2 Installation and operating instructions BM 100 A Contents 1 Mechanical
20 Installation and operating instructions BM 100 A • 1 RS 485 output with / without optional passive analogue current output for
Installation and operating instructions BM 100 A 21 3 User Interface The BM 100 A may be configured and operated using a user interface se
22 Installation and operating instructions BM 100 A 3.3 Status Markers This line of numbers identifies six types of errors by means of a
Installation and operating instructions BM 100 A 23 4 BM 100 A technical data 4.1 Technical data Input Measured variable Distance, level
24 Installation and operating instructions BM 100 A Power supply Option 1 24 V DC / AC, +10%/-15%, Power used: 9W Option 2 100 – 240
Installation and operating instructions BM 100 A 25 4.2 BM100A Equipment Architecture Single cable Ø8mm (K) Single 316 stainless steel f
26 Installation and operating instructions BM 100 A Single cable Ø8mm (K) No spacer D45x245(316L) D12x1500(316L) Turnbuckle (316L) With
Installation and operating instructions BM 100 A 27 4.3 Probe measurement limits Probe measurement limi
28 Installation and operating instructions BM 100 A 4.4 Gauge dimensions The drawing below illustrates the complete set of standard gauge
Installation and operating instructions BM 100 A 29 If you need to return a device for testing or repair to KROHNE Your instrument has be
Installation and operating instructions BM 100 A 3 General advice on safety The device will normally weigh between approx. 11 kg / 25 lb
4 Installation and operating instructions BM 100 A Principal gauge components Non-Ex version Ex version 1 Cable entry (output)
Installation and operating instructions BM 100 A 5 Standard nameplate Items supplied • signal converter connected to a
6 Installation and operating instructions BM 100 A 1 Mechanical installation 1.1 Handling and storage Caution : The probe is a critical
Installation and operating instructions BM 100 A 7 1.2 Installation restrictions Hazardous-duty systems (Ex, FM…): • refer to the supple
8 Installation and operating instructions BM 100 A Nozzles extending into tank Caution: Do not use nozzles that extend into the tank. Th
Installation and operating instructions BM 100 A 9 Probe Type Recommended minimum distance of probe from objects inside the tank in milli