Installation and operating instructionsIFC 110 F V2.0IFC 110 F-EEx V2.0Signal converters for electromagnetic flowmetersApplicable toSoftware Versions●
10 IFC 110 F 05/2003 1.3.5 Connection diagrams for power supply and flow sensors Important remarks for circuit diagrams PLEASE NOTE ! •
05/2003 IFC 110 F 11 Process temperature below 150°C (302°F) I Signal cable A (type DS) II Signal cable B (type BTS) IFC 110 F
12 IFC 110 F 05/2003 1.3.6 EEx-Connection diagrams for power supply and flow sensors PLEASE NOTE! • The figures in brackets indicate the stra
05/2003 IFC 110 F 13 Process temperature below 150°C (302°F) I Signal cable A (type DS) II Signal cable B (type BTS) IFC 110 F
14 IFC 110 F 05/2003 2 Electrical connection: outputs and inputs IMPORTANT! For EEx versions, also pay regard to all directions included in Se
05/2003 IFC 110 F 15 2.2 Current output I • The current output is electrically isolated from all other circuits. • Setting data and functio
16 IFC 110 F 05/2003 2.3 Pulse outputs P and A1 2.3.1 Pulse output P for electronic totalizers (EC) • Pulse output P is electrically isolate
05/2003 IFC 110 F 17 2.3.2 Pulse output A1 for electromechanical totalizers (EMC) PLEASE NOTE: The output terminal A1 can be used as status o
18 IFC 110 F 05/2003 2.4 Status outputs A1 / A2 / D1 / D2 PLEASE NOTE: The output terminal A1 can be used as status output A1 or as a 2nd pulse
05/2003 IFC 110 F 19 2.6 Connection diagrams of outputs and inputs IMPORTANT! For EEx versions, also pay regard to all directions included in
2 IFC 110 F 05/2003 Signal converter versions The operating data are factory-set to your ordered specifications. IFC 110 F / D Standard versio
20 IFC 110 F 05/2003 { Current output Iactive | Current output Iactive with automatic range change BA without external change-over relay }
05/2003 IFC 110 F 21 Pulse output Pactive Pulse output Pactive for electronic totalizers (EC) for frequencies ≤ 1 kHz for electronic tot
22 IFC 110 F 05/2003 Status outputs D1 / D2 / A1 / A2 active Status outputs D1 / D2 / A1 / A2 passive I ≤ 100 mA Uext. ≤ 32 V DC / ≤ 24 V AC
05/2003 IFC 110 F 23 3 Start-up • Before connecting to power, check that the instrument is correctly installed as described in Sections 1 and
24 IFC 110 F 05/2003 4 Operating of the signal converter 4.1 KROHNE operating concept
05/2003 IFC 110 F 25 4.2 Operating and control elements The instrument can be operated by means of ... … the 1
26 IFC 110 F 05/2003 4.3 Key functions In the following, the cursor or flashing part of the display is shown against a grey background. To star
05/2003 IFC 110 F 27 To change numbers increase number 3 9 7. 3 5 ↑
28 IFC 110 F 05/2003 4.4 Table of settable functions Abbreviations used: A1, A2 Status outputs P (P2) Pulse output (2nd pulse output A1) (A1
05/2003 IFC 110 F 29 Fct. Text Description and setting 1.04 DISPLAY Display functions → DISP.FLOW Selection of flow display ● NO DISP. ●
05/2003 IFC 110 F 3 System description Electromagnetic flowmeters are precision instruments designed for linear flow measurement of liquid prod
30 IFC 110 F 05/2003 Fct. Text Description and setting 1.08 STATUS A2 Status outputs A2, D1 and D2 1.09 STATUS D1 Description of function of
05/2003 IFC 110 F 31 Fct. Text Description and setting 1.07 STATUS A1 Status output A1 (terminal A1 connected as status output A1 or as a 2nd
32 IFC 110 F 05/2003 Fct. Text Description and setting 3.0 INSTALL. Installation menu 3.01 LANGUAGE Select language for display texts ●
05/2003 IFC 110 F 33 Fct. Text Description and setting 3.05 USER UNIT Set any required unit for flowrate and counting → TEXT VOL. Set text f
34 IFC 110 F 05/2003 Fct. Text Description and setting → LIMIT VAL. Set limit value for noise/interference suppression (appears only when
05/2003 IFC 110 F 35 4.6 Resetting the totalizer and deleting error messages, RESET/QUIT menu Delete error messages in RESET/QUIT menu Key
36 IFC 110 F 05/2003 6 Special Applications, Functional Checks, Service and Order Numbers 6.1 Use in hazardous areas 6.1.1 General Signal con
05/2003 IFC 110 F 37 6.1.3 Installation and electrical connection Type IFC 110 F - EEx signal converters are type tested as associated electrica
38 IFC 110 F 05/2003 10 Technical data 10.1 Signal converter Mode of operation and system structure Measurement principle Faraday’s law of
05/2003 IFC 110 F 39 Status outputs (passive) D1 / D2 / A2 A1 (can also be operated as pulse output) Function, set for trip point trip point
4 IFC 110 F 05/2003 1 Electrical connection: power supply 1.1 Location and important installation notes ……………………. PLEASE NOTE ! • Electrical
40 IFC 110 F 05/2003 10.2 Error limits Display, digital values, pulse output F maximum error in % of measured value (MV), not typical values v
05/2003 IFC 110 F 41 10.3 Dimensions and weights IFC 110 F / IFC 110 F-EEx and ZD / ZD-EEx Dimensions in mm and inch IFC 110 F Sig
42 IFC 110 F 05/2003 13 Approvals 13.1 EC-type examination certificate English translation 13.2 EC-type examination certificate German origin
05/2003 IFC 110 F 43 If you need to return flowmeters for testing or repair to KROHNE Your electromagnetic flowmeter • has been carefully manu
05/2003 IFC 110 F 5 1.2 Power supply - connection PLEASE NOTE ! • Type of enclosure IP 65 to IEC 529 / EN 60529 equivalent to NEMA 4/4X. •
6 IFC 110 F 05/2003 1.3 Electrical connection of flow sensors 1.3.1 General remarks on signal lines A and B and field current line C Proper o
05/2003 IFC 110 F 7 1.3.2 Stripping (preparation) of signal cables Please note: The numbers in the drawings designate the stranded drain wires
8 IFC 110 F 05/2003 1.3.3 Grounding of flow sensor • The flow sensor must be correctly connected to ground. • The grounding cable may not tra
05/2003 IFC 110 F 9 1.3.4 Cable lengths (max. distance between signal converter and flow sensor) Abbreviations and explanations The abbreviatio