Krohne OPTISWITCH 3100C NAMUR EN User Manual

Browse online or download User Manual for Equipment Krohne OPTISWITCH 3100C NAMUR EN. KROHNE OPTISWITCH 3100C NAMUR EN User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instructions

Operating InstructionsOPTISWITCH 3100 Cwith NAMUR output

Page 2 - Contents

4 Mounting4.1 General instructionsIn general, OPTISWITCH 3100 C can be mounted in anyposition. The instrument must be mounted in such a way thatthe vi

Page 3

The vibrating level switch is a measuring instrument and mustbe treated accordingly. Bending the vibrating element willdestroy the instrument.Warning:

Page 4 - 1 Sequence

In abrasive solids, mounting according to illustration b. hasproven. A spout forms in the concave protective sheetpreventing wear of the protective sh

Page 5 - 2 For your safety

12Fig. 5: Orientation of the tuning fork in case of flow1 Marking with screwed version2 Direction of flowIn case of horizontal mounting in adhesive prod

Page 6 - 2.6 SIL conformity

>125Fig. 7: Baffle protection against damages14 OPTISWITCH 3100 C - with NAMUR outputMounting31356-EN-060830

Page 7 - 3 Product description

5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li

Page 8 - 3.3 Operation

3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t

Page 9 - 3.4 Storage and transport

14442 3Fig. 9: Material versions, single chamber housing1 Plastic2 Aluminium3 Stainless steel4 Filter element for pressure compensationSimulationNAMUR

Page 10 - 4 Mounting

1 2++--Fig. 11: Wiring plan, single chamber housingExternal simulation keyIn addition to the test key on the oscillator, you can connect anexternal ke

Page 11 - 4.2 Mounting instructions

6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.On the electronics module you will find the following indicatingand adj

Page 12 - 31356-EN-060830

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13

light-weight solids, turn the potentiometer to the left stop(>0.008 g/cm³ or >0.0003 lbs/in³). OPTISWITCH 3100 C willthus be more sensitive and

Page 14

Note:The mode on the NAMUR amplifier must be set so that theswitching output goes to safe condition in case a faultmessage is received (I <=1 mA).Le

Page 15 - 5.2 Connection steps

sequence of the switching conditions must be monitored viathe switching amplifier as well as the connected systems. Thesensor must neither be removed n

Page 16

(after releasing the simulation key)Sensor cur-rentLevel relayamplifier -overfill pro-tectionLevel relayamplifier -dry runprotectionSignal lampamplifier -

Page 17

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH3100 C is completely maintenance free.7.2 Rect

Page 18

l Wrong characteristics selectedà Set the correct characteristics on the characteristicsreversal switch (overfill protection; dry run protection).Wirin

Page 19 - 6 Set up

21Fig. 15: Loosen the screws1 Electronics module2 Screws (2 pcs.)6 Remove the old oscillator7 Compare the new oscillator with the old one. The type la

Page 20 - 6.3 Function chart

7.4 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form from our websitehttp://www.krohne-mar.com/filea

Page 21 - 6.4 Recurring function test

8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high

Page 22

9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process

Page 23

9 Supplement9.1 Technical data...299.2 Dimensions ...33Supplementary operating instructions manualsInfor

Page 24 - 7.2 Rectify faults

Ambient conditionsAmbient temperature on the housing -40 … +80 °C (-40 … +176 °F)Storage and transport temperature -40 … +80 °C (-40 … +176 °F)Process

Page 25 - ? Signal lamp flashes yellow

123-50˚C(-58˚F)50˚C(122˚F)40˚C(104˚F)-40˚C(-40˚F)80˚C(176˚F)0˚C(32˚F)100˚C(212˚F)150˚C(302˚F)200˚C(392˚F)250˚C(482˚F)Fig. 17: Ambient temperature - Pr

Page 26

Potentiometer for switching point adap-tation0.02 … 0.1 g/cm³ (0.0007 … 0.036 lbs/in³)Simulation key simulation of a line break between sensor andproc

Page 27 - 7.4 Instrument repair

9.2 DimensionsOPTISWITCH 3100 C112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32&quo

Page 28 - 8 Dismounting

22mm(55/64")33mm(1 19/64")220mm (8 21/32")150mm (5 29/32")G1½Aø 43mm (1 11/16")Fig. 19: OPTISWITCH 3100 C, threaded version G

Page 29 - 9 Supplement

178mm (7 1/64")ø 34mm (1 11/32")Fig. 20: Temperature adapterSupplementOPTISWITCH 3100 C - with NAMUR output 3531356-EN-060830

Page 30

Subject to change without notice31356-EN-060830

Page 31

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 32

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 33 - 9.2 Dimensions

2.6 SIL conformityOPTISWITCH 3100 C fulfills the requirements of functionalsafety according to IEC 61508/IEC 61511. You can find furtherinformation in t

Page 34

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 3100 C level sensorl Documentation- this operating instructions ma

Page 35

It functions even when exposed to strong external vibration orchanging products.Solid detection in waterIf OPTISWITCH 3100 C was ordered for detection

Page 36

l Simulation key3.4 Storage and transportYour instrument was protected by packaging during transport.Its capacity to handle normal loads during transp

Comments to this Manuals