Battery powered electromagnetic flowmeterOPTIFLUX 2070Quick Start
OPTIFLUX 2070 7309992100 10Torques and pressuresNominal size D N [ m m ]
OPTIFLUX 2070www.krohne.com 11Max. torque:• Step 1: approx. 50% of max. torque• Step 2: approx. 80% of max. torque• Step 3: 100% of max. torque give
OPTIFLUX 2070 7309992100 12Terminal assignment of IFC 070
OPTIFLUX 2070www.krohne.com 13Electrical values1 Status output 12 Status output 23 Not connected4 Ground5 Pulse output A6 Pulse output BPulse
OPTIFLUX 2070 7309992100 14Signal and field current cable for remote versionCable connection for field version: flow sensor side• Prepare appropriate
OPTIFLUX 2070www.krohne.com 15• Connect the shield to terminal 1, the purple cable to terminal 2 and the blue to terminal 3.Cable connection for fie
OPTIFLUX 2070 7309992100 16• Connect the shield to terminal 1, the purple cable to terminal 2 and the blue to terminal 3.
OPTIFLUX 2070www.krohne.com 17Connection of battery• remove the blue protection cap of the converter • remove the 4 Allen bolts (4 mm)• remove the c
OPTIFLUX 2070 7309992100 18• tighten the 4 Allen bolts• replace the blue protection capDisplay and operating elementsWARNING!Make sure that the batte
OPTIFLUX 2070www.krohne.com 19Programming• Display test: press Z button 2x 1s• Software version: press Z button 1x 1sNOTE!KROHNE programs the signa
OPTIFLUX 2070 7309992100 2General safety notesYou can find the newest and/or additional information on the CD-ROM provided, in the handbook, the data
OPTIFLUX 2070 7309992100 20ContactKROHNE AltometerKROHNE AltometerKROHNE AltometerKROHNE AltometerKerkeplaat 123313 LC DordrechtPostbus 1103300 AC Do
OPTIFLUX 2070www.krohne.com 3Visual checkScope of delivery1 OPTIFLUX 2070 with blue protection cap2 Quick Start3 Factory calibration report4 CD-
OPTIFLUX 2070 7309992100 4TransportInlet and outlet 1 ≥ 5 DN2 ≥ 2 DN
OPTIFLUX 2070www.krohne.com 5Mounting position and flange deviation1 Lmax2 LminCAUTION!Max. permissible deviation of pipe flange faces: Lmax - Lmi
OPTIFLUX 2070 7309992100 6VibrationMagnetic field
OPTIFLUX 2070www.krohne.com 7BendsOpen discharge
OPTIFLUX 2070 7309992100 8T-sectionControl valve1 ≥ 10 DN
OPTIFLUX 2070www.krohne.com 9PumpGrounding1 Metal pipelines, not internally coated. Grounding without grounding rings!2 Metal pipelines with inter