Operating InstructionsOPTISWITCH 5200 C, 5250 Cwith NAMUR output
4 Mounting4.1 General instructionsIn general, OPTISWITCH 5200 C, 5250 C can be mounted inany position. The instrument must be mounted in such a waytha
1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw
condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c
4.2 Mounting instructionsOPTISWITCH 5200 C, 5250 C has a defined thread startingpoint. This means that every OPTISWITCH 5200 C, 5250 C isin the same fo
When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo
a longer tube version be necessary, you can provide a suitablesupport or guy directly above the tuning fork to secure theextension tube.This measure a
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t
SW E60NNAMUR(IEC 60947-5-6)max.min.Simul.+-120,5 g / cm30,7 g / cm3356124Fig. 11: Electronics and connection compartment, single chamber housing1 Cont
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching condition of the electronics can be checked onthe plasti
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
Single-colour control lamp (LED) for indication of the switchingconditionl red = High current >= 2.2 mAl dark = Low current <=1 mAl red (flashing
6.3 Function chartThe following chart provides an overview of the switchingconditions depending on the adjusted mode and level.Note:The mode on the NA
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5200 C, 5250 C is completely maintenance free.
l Wrong characteristics selectedà Set the correct characteristics on the characteristicsreversal switch (overfill protection; dry run protection).Wirin
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello
Layer thickness- Enamel approx. 0.8 mm (0.03 in)- ECTFE approx. 0.5 mm (approx. 0.02 in)- PFA approx. 0.5 mm (approx. 0.02 in)Surface quality- Standar
Integration time approx. 500 msFrequency approx. 1200 HzAmbient conditionsAmbient temperature on the housing -40 … +70 °C (-40 … +158 °F)Storage and t
Viscosity - dynamic 0.1 … 10,000 mPas(requirement: with density1)Density 0.7 … 2.5 g/cm³ (0.025 … 0.09 lbs/in³);0.5 … 2.5 g/cm³ (0.018 … 0.09 lbs/in³)
Overvoltage category IIIProtection class IIApprovals2)ATEX II 1G, 1/2G, 2GEExiaIIC T6ATEX II 1/2G, 2GEExd d IIC T63)Overfill protection acc. to WHGShip
9 Supplement9.1 Technical data...259.2 Dimensions ...30OPTISWITCH 5200 C, 5250 C - with NAMUR output 3Co
9.2 DimensionsHousing112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32")~ 116mm
OPTISWITCH 5200 C, 5250 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")LLLLL32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1
Supplement32 OPTISWITCH 5200 C, 5250 C - with NAMUR output30434-EN-060831
SupplementOPTISWITCH 5200 C, 5250 C - with NAMUR output 3330434-EN-060831
Supplement34 OPTISWITCH 5200 C, 5250 C - with NAMUR output30434-EN-060831
SupplementOPTISWITCH 5200 C, 5250 C - with NAMUR output 3530434-EN-060831
Subject to change without notice30434-EN-060831
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 SIL conformityOPTISWITCH 5200 C, 5250 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5200 C, 5250 C level sensorl Documentation- this operating instruc
It is designed for industrial use in all areas of processtechnology and can be used in liquids.Typical applications are overfill and dry run protection
3.3 OperationThe switching condition of OPTISWITCH 5200 C, 5250 C withplastic housing can be checked when the housing is closed(signal lamp). With the