Operating InstructionsOPTISWITCH 5200 C, 5250 Cwith relay output

Page 2 - Contents

4 Mounting4.1 General instructionsIn general, OPTISWITCH 5200 C, 5250 C can be mounted inany position. The instrument must be mounted in such a waytha

Page 3

1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw

Page 4 - 1 Sequence

condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c

Page 5 - 2 For your safety

4.2 Mounting instructionsOPTISWITCH 5200 C, 5250 C has a defined thread startingpoint. This means that every OPTISWITCH 5200 C, 5250 C isin the same fo

Page 6 - 2.6 SIL conformity

When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo

Page 7 - 3 Product description

a longer tube version be necessary, you can provide a suitablesupport or guy directly above the tuning fork to secure theextension tube.This measure a

Page 8

5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li

Page 9 - 3.4 Storage and transport

1 Unscrew the housing cover2 Loosen compression nut of the cable entry3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) in

Page 10 - 4 Mounting

35124SW E60R20-253V AC20-72V DCABLN12 345 6780,5 g / cm30,7 g / cm33 4 5 6 7 8+Fig. 11: Electronics and connection compartment, single chamber housing

Page 11 - 30431-EN-060831

6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching condition of the electronics can be checked onthe plasti

Page 12

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13 - 4.2 Mounting instructions

Control lamp (LED) for indication of the switching conditionl green = relay energizedl red = relay deenergizedl red (flashing) = failureWith the mode a

Page 14

Level Switching status Control lampFailure of the sup-ply voltage(mode A/B)any53 4(8)(6) (7)Relay deenergizedFailure any53 4(8)(6) (7)Relay deenergize

Page 15

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5200 C, 5250 C is completely maintenance free.

Page 16 - 5.2 Connection steps

l Wrong mode selectedà Set the correct mode on the mode switch (max.: overfillprotection; min.: dry run protection). Wiring should becarried out accord

Page 17

8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high

Page 18

9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello

Page 19 - 6 Set up

Layer thickness- Enamel approx. 0.8 mm (0.03 in)- ECTFE approx. 0.5 mm (approx. 0.02 in)- PFA approx. 0.5 mm (approx. 0.02 in)Surface quality- Standar

Page 20 - 6.3 Function chart

Breaking capacity- min. 50 mW- max.750 VA AC, 54 WDCIf inductive loads or stronger currents areswitched through, the gold plating on the relaycontact

Page 21 - (8)(6) (7)

- OPTISWITCH 5200 C, 5250 C withECTFE coating-50 … +150 °C (-58 … +302 °F)- OPTISWITCH 5200 C, 5250 C withPFA coating-50 … +150 °C (-58 … +302 °F)123-

Page 22 - 7.2 Rectify faults

Adjustment elementsMode switch- AMax. detection or overflow/overfill protection- BMin. detection or dry run protectionDensity switch- 0.50.5 … 2.5 g/cm³

Page 23 - ? Signal lamp flashes red

9 Supplement9.1 Technical data...259.2 Dimensions ...30OPTISWITCH 5200 C, 5250 C - with relay output 3Co

Page 24 - 8 Dismounting

9.2 DimensionsOPTISWITCH 5200 C, 5250 C112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 2

Page 25 - 9 Supplement

OPTISWITCH 5200 C, 5250 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")LLLLL32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1

Page 26

Supplement32 OPTISWITCH 5200 C, 5250 C - with relay output30431-EN-060831

Page 27

SupplementOPTISWITCH 5200 C, 5250 C - with relay output 3330431-EN-060831

Page 28

Supplement34 OPTISWITCH 5200 C, 5250 C - with relay output30431-EN-060831

Page 29

SupplementOPTISWITCH 5200 C, 5250 C - with relay output 3530431-EN-060831

Page 30 - 9.2 Dimensions

Subject to change without notice30431-EN-060831

Page 31 - OPTISWITCH 5200 C, 5250 C

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 32

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 33

2.6 SIL conformityOPTISWITCH 5200 C, 5250 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat

Page 34

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5200 C, 5250 C level sensorl Documentation- this operating instruc

Page 35

It is designed for industrial use in all areas of processtechnology and can be used in liquids.Typical applications are overfill and dry run protection

Page 36

3.3 OperationThe switching condition of OPTISWITCH 5200 C, 5250 C withplastic housing can be checked when the housing is closed(signal lamp). With the