Operating InstructionsOPTISOUND 3010 C4 ... 20 mA/HART - four-wire
4 Mounting4.1 General instructionsSelect an installation position you can easily reach formounting and connecting as well as later retrofitting of anin
12Fig. 3: Min. distance to the max. level1 Dead zone2 Reference planeInformation:If the product reaches the transducer, buildup can form on itover a p
4.2 Mounting informationScrew OPTISOUND 3010 C into the mounting socket with anappropriate spanner applied to the hexagon of the processfitting. Max. t
Fig. 6: Vessel with conical bottomThe mounting socket should preferably be dimensioned toallow the lower edge of the transducer to protrude at least 1
> 10 mmdhdh100 mm/4"150 mm/6"300 mm/12"400 mm/16"Fig. 8: Deviating socket dimensionsIn liquids, direct the sensor as perpendicu
The ultrasonic sensor should be installed at a location whereno installations cross the ultrasonic beam.Vessel installations such as for example, ladd
Fig. 12: AgitatorsDo not mount the instruments in or above the filling stream.Make sure that you detect the product surface and not theinflowing product
Guided radar is not influenced by foam generation and isparticularly suitable for such applications.If there are strong air currents in the vessel, e.g
5 Connecting to power supply5.1 Preparing the connectionAlways observe the following safety instructions:l Connect only in the complete absence of lin
If potential equalisation currents are expected, the connectionon the evaluation side must be made via a ceramic capacitor(e.g. 1 nF, 1500 V). The low
Contents1 About this document1.1 Function ...51.2 Target group ...51.3 Symbolism used ...
Fig. 15: Connection steps 5 and 65.3 Wiring plans, double chamber housing1 2 345Fig. 16: Double chamber housing1 Housing cover, connection compartment
1Display12 5678I2CFig. 17: Electronics compartment, double chamber housing1 Internal connection cable to the connection compartment12Display12I2CFig.
4 ... 20 mAPE/ L/ NL1 NGND1 212344...20mA ISFig. 19: Wiring plan, double chamber housing1 Supply voltage2 Signal output5.4 Switch on phaseAfter OPTISO
6 Setup with the indicating/adjustmentmodule6.1 Short descriptionThe indicating/adjustment module is used for measured valuedisplay, adjustment and di
Fig. 20: Installation of the indicating/adjustment moduleNote:If you intend to retrofit OPTISOUND 3010 C with an indicating/adjustment module for conti
6.3 Adjustment system1.1231Fig. 21: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- mo
6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) theaddress must be set before continuing with the parameteradjustment. You wi
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [–>] andconfirm with [OK]. Now the menu item
vessel wall (with solids). To adapt the sensor to these differentconditions, you should first select in this menu item "Liquid" or"Solid&
Enter the requested parameter via the appropriate keys, saveyour settings and jump to the next menu item with the [–>] key.A linearization is neces
8 Dismounting8.1 Dismounting procedure ...378.2 Disposal ...379 Supplement9.1 Technical data...
False signal suppressionChange now?Proceed as follows:1 Move from the measured value display to the main menuby pushing [OK].2 Select the menu item &q
6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Min. adjustment0.00 %=4.000 m(d)3.000 m(d)1.2Max. adjustment100.00
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1False signal suppressionChange now?4.2Addl. adjustmentsnone4.3Current outputOutput mode 4-20
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISOUND3010 C is completely maintenance-free.7.2 Fault
? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return it for repairIn Ex applications,
If there is no electronics module available on site, it can beordered from the responsible Krohne agency.7.4 Instrument repairIf a repair is necessary
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterials, wetted parts- Process fitting Thread G1½A and 1½ NPT: PVDF- Transducer PVDF- Seal transducer/proce
Accuracy (similar to DIN EN 60770-1)Reference conditions acc. to DIN EN 61298-1- Temperature 18 … +30°C (64 … +86°F)- Relative humidity 45 … 75 %- Atm
Process conditionsVessel pressure -20 … 200 kPa (-0.2 … 2.0 bar/-2.9 … 29 psi)Process temperature (transducer tem-perature)-40 … +80°C (-40 … +176°F)V
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation of OPTISOUND 30
Approvals6)7)ATEX ATEX II 1G, 1/2G, 2GEExiaIIC T66)Deviating data with Ex applications: see separate safety instructions.7)Depending on order specifica
9.2 DimensionsOPTISOUND 3010 C1 2155mm (6 7/64")22mm (55/64")66mm(2 19/32")ø 39mm(1 17/32")ø 74mm(2 58/64")60mm(2 23/64"
9.3 CertificateCE declaration of conformityFig. 24: CE declaration of conformity42 OPTISOUND 3010 C - 4 ... 20 mA/HART - four-wireSupplement30504-EN-05
OPTISOUND 3010 C - 4 ... 20 mA/HART - four-wire 43Supplement30504-EN-050914
Subject to change without notice30504-EN-050914
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained, specialise
The parameter adjustment of the basic sensor functions isindependent of the software version. The range of availablefunctions depends on the respectiv
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISOUND 3010 C ultrasonic sensorl Documentation- this operating instruction
3.2 Principle of operationOPTISOUND 3010 C is an ultrasonic sensor for continuouslevel measurement. It is suitable for liquids and solids invirtually
l Relative humidity 20 … 85 %OPTISOUND 3010 C - 4 ... 20 mA/HART - four-wire 9Product description30504-EN-050914