4 Mounting4.1 General instructionsIn general, OPTISWITCH 5200 C, 5250 C can be mounted inany position. The instrument must be mounted in such a waytha
1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw
condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c
4.2 Mounting instructionsOPTISWITCH 5200 C, 5250 C has a defined thread startingpoint. This means that every OPTISWITCH 5200 C, 5250 C isin the same fo
When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo
a longer tube version be necessary, you can provide a suitablesupport or guy directly above the tuning fork to secure theextension tube.This measure a
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t
SW E60Z+120,5 g / cm30,7 g / cm311-36V DC4123Fig. 11: Electronics and connection compartment, single chamber housing1 Control lamp2 DIL switch for sen
cates. If OPTISWITCH with oscillator SW E60ZEX, SW E60ZEX E1 should be operated directly on the analogue input of aPLC, a suitable safety barrier shou
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching status of the electronics can be checked whenthe cover o
6.2 Adjustment elements1212Fig. 13: Oscillator SW E60Z - two-wire output1 Signal lamp (LED)2 DIL switch for sensitivity adjustmentControl lamp (LED) f
Mode onthe signalcondition-ing instru-mentLevel Signalcurrent -SensorAnalogueinput con-trol1)Signallamp -sensorSignallamp -signalcondi-tioninginstru-m
The following instrument combinations meet the requirementsacc. to WHG:OPTISWITCH 5200 C, 5250 CEXwithl Oscillator SWE60ZEXl signal conditioning instr
on correct function. The following operating conditions aresimulated during the test:l Fault signall Empty signall Full signalCheck if all three switc
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5200 C, 5250 C is completely maintenance free.
l Wrong mode selectedà Set the correct mode on the mode switch (max.: overfillprotection; min.: dry run protection). Wiring should becarried out accord
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello
Layer thickness- Enamel approx. 0.8 mm (0.03 in)- ECTFE approx. 0.5 mm (approx. 0.02 in)- PFA approx. 0.5 mm (approx. 0.02 in)Surface quality- Standar
9 Supplement9.1 Technical data...289.2 Dimensions ...32OPTISWITCH 5200 C, 5250 C - with two-wire output
Ambient conditionsAmbient temperature on the housing -40 … +70 °C (-40 … +158 °F)Storage and transport temperature -40 … +80 °C (-40 … +176 °F)Process
0.5 … 2.5 g/cm³ (0.018 … 0.09 lbs/in³) byswitching overElectromechanical dataCable entry/plug2)- Single chamber housing l 1x cable entry M20x1.5 (cabl
9.2 DimensionsHousing112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32")~ 116mm
OPTISWITCH 5200 C, 5250 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")LLLLL32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1
Supplement34 OPTISWITCH 5200 C, 5250 C - with two-wire output30435-EN-060831
SupplementOPTISWITCH 5200 C, 5250 C - with two-wire output 3530435-EN-060831
Subject to change without notice30435-EN-060831
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 SIL conformityOPTISWITCH 5200 C, 5250 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5200 C, 5250 C level sensorl Documentation- this operating instruc
It is designed for industrial use in all areas of processtechnology and can be used in liquids.Typical applications are overfill and dry run protection
3.3 OperationThe switching condition of OPTISWITCH 5200 C, 5250 C withplastic housing can be checked when the housing is closed(signal lamp). With the