Operating InstructionsOPTISWITCH 5100 C, 5150 Cwith NAMUR output
4 Mounting4.1 General instructionsIn general, OPTISWITCH 5100 C, 5150 C can be mounted inany position. The instrument must be mounted in such a waytha
1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw
condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c
4.2 Mounting instructionsOPTISWITCH 5100 C, 5150 C has a defined thread startingpoint. This means that every OPTISWITCH 5100 C, 5150 C isin the same fo
When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t
SW E60NNAMUR(IEC 60947-5-6)max.min.Simul.+-120,5 g / cm30,7 g / cm3356124Fig. 9: Electronics and connection compartment, single chamber housing1 Contr
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching condition of the electronics can be checked onthe plasti
Single-colour control lamp (LED) for indication of the switchingconditionl red = High current >= 2.2 mAl dark = Low current <=1 mAl red (flashing
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
6.3 Function chartThe following chart provides an overview of the switchingconditions depending on the adjusted mode and level.Note:The mode on the NA
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5100 C, 5150 C is completely maintenance free.
l Wrong characteristics selectedà Set the correct characteristics on the characteristicsreversal switch (overfill protection; dry run protection).Wirin
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello
Surface quality- Standard Raapprox. 3 µm (approx. 1.18-4in)- Hygienic version 3A (OPTISWITCH5150 C)Ra<0.8 µm (<3.15-5in)Process fittings- Thread
Ambient conditionsAmbient temperature on the housing -40 … +70 °C (-40 … +158 °F)Storage and transport temperature -40 … +80 °C (-40 … +176 °F)Process
0.5 … 2.5 g/cm³ (0.018 … 0.09 lbs/in³) byswitching overElectromechanical dataCable entry/plug1)- Single chamber housing l 1x cable entry M20x1.5 (cabl
Approvals2)ATEX II 1G, 1/2G, 2GEExiaIIC T6ATEX II 1/2G, 2GEExd d IIC T63)Overfill protection acc. to WHGShip approvals2)Deviating data in Ex applicatio
9.2 DimensionsHousing112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32")~ 116mm
9 Supplement9.1 Technical data...249.2 Dimensions ...29OPTISWITCH 5100 C, 5150 C - with NAMUR output 3Co
OPTISWITCH 5100 C, 5150 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1 31/3
SupplementOPTISWITCH 5100 C, 5150 C - with NAMUR output 3130429-EN-060831
Subject to change without notice30429-EN-060831
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 SIL conformityOPTISWITCH 5100 C, 5150 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5100 C, 5150 C level sensorl Documentation- this operating instruc
Thanks to its simple and robust measuring system, OPTI-SWITCH 5100 C, 5150 C is virtually unaffected by thechemical and physical properties of the liqu
l Control lamp for indication of the switching condition.l DIL switch for sensitivity adjustmentl Mode switch to select the switching condition (rever