Operating InstructionsOPTISWITCH 5100 C, 5150 Cwith transistor output
4 Mounting4.1 General instructionsIn general, OPTISWITCH 5100 C, 5150 C can be mounted inany position. The instrument must be mounted in such a waytha
1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw
condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c
4.2 Mounting instructionsOPTISWITCH 5100 C, 5150 C has a defined thread startingpoint. This means that every OPTISWITCH 5100 C, 5150 C isin the same fo
When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t
SW E60T10-55V DC1 PNP2 3 4 1 NPN234AB0,5 g / cm30,7 g / cm3max 400mAout12 34+++35124Fig. 9: Electronics and connection compartment, single chamber hou
+ -1234+-Fig. 11: PNP action18 OPTISWITCH 5100 C, 5150 C - with transistor outputConnecting to voltage supply30427-EN-060831
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching condition of the electronics can be checked onthe plasti
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
Control lamp (LED) for indication of the switching conditionl green = output conductsl red = output blocksl red (flashing) = failureWith the mode adjus
Level Switching status Control lampFailure of the sup-ply voltage(mode A/B)any transistor blocksFailure any transistor blocksflashes redOPTISWITCH 5100
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5100 C, 5150 C is completely maintenance free.
l Wrong mode selectedà Set the correct mode on the mode switch (max.: overfillprotection; min.: dry run protection). Wiring should becarried out accord
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello
Process fittings- Thread G¾ A, ¾ NPT, G1 A, 1 NPT- Flanges DIN from DN 25, ANSI from 1"- hygienic fittings Bolting DN 40 PN 40, Tri-Clamp 1",
OPTISWITCH 5100 C, 5150 C of 316L/Hastelloy C4 (2.4610)-50 … +150 °C (-58 … +302 °F)Process temperature (thread or flangetemperature) with temperature
Electromechanical dataCable entry/plug1)- Single chamber housing l 1x cable entry M20x1.5 (cable-ø 5 … 9 mm),1x blind stopper M20x1.5or:l 1x closing c
9.2 DimensionsHousing112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32")~ 116mm
9 Supplement9.1 Technical data...259.2 Dimensions ...29OPTISWITCH 5100 C, 5150 C - with transistor outpu
OPTISWITCH 5100 C, 5150 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1 31/3
SupplementOPTISWITCH 5100 C, 5150 C - with transistor output 3130427-EN-060831
Subject to change without notice30427-EN-060831
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 SIL conformityOPTISWITCH 5100 C, 5150 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5100 C, 5150 C level sensorl Documentation- this operating instruc
Thanks to its simple and robust measuring system, OPTI-SWITCH 5100 C, 5150 C is virtually unaffected by thechemical and physical properties of the liqu
On the electronics module you will find the following indicatingand adjustment elements:l signal lamp for indication of the switching condition (green/