Operating InstructionsOPTISWITCH 5100 C, 5150 Cwith relay output
4 Mounting4.1 General instructionsIn general, OPTISWITCH 5100 C, 5150 C can be mounted inany position. The instrument must be mounted in such a waytha
1Fig. 3: Horizontal mounting1 Switching point12Fig. 4: Horizontal mounting (recommended installation location - particularly foradhesive products)1 Sw
condensation water can thus drain off. This applies mainly tomounting outdoors, in areas where moisture is expected (e.g.by cleaning processes) or on c
4.2 Mounting instructionsOPTISWITCH 5100 C, 5150 C has a defined thread startingpoint. This means that every OPTISWITCH 5100 C, 5150 C isin the same fo
When used in adhesive and viscous products, the tuning forkshould protrude into the vessel to avoid buildup. For thatreason, sockets for flanges and mo
5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li
1 Unscrew the housing cover2 Loosen compression nut of the cable entry3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) in
35124SW E60R20-253V AC20-72V DCABLN12 345 6780,5 g / cm30,7 g / cm33 4 5 6 7 8+Fig. 9: Electronics and connection compartment, single chamber housing1
6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.The switching condition of the electronics can be checked onthe plasti
Control lamp (LED) for indication of the switching conditionl green = relay energizedl red = relay deenergizedl red (flashing) = failureWith the mode a
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
Level Switching status Control lampFailure of the sup-ply voltage(mode A/B)any53 4(8)(6) (7)Relay deenergizedFailure any53 4(8)(6) (7)Relay deenergize
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH5100 C, 5150 C is completely maintenance free.
l Wrong mode selectedà Set the correct mode on the mode switch (max.: overfillprotection; min.: dry run protection). Wiring should becarried out accord
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L, Hastello
Surface quality- Standard Raapprox. 3 µm (approx. 1.18-4in)- Hygienic version 3A (OPTISWITCH5150 C)Ra<0.8 µm (<3.15-5in)Process fittings- Thread
Modes (adjustable)- AMax. detection or overflow/overfill protection- BMin. detection or dry run protectionMeasuring accuracyHysteresis approx. 2 mm (0.0
123-50˚C(-58˚F)50˚C(122˚F)40˚C(104˚F)-40˚C(-40˚F)70˚C(158˚F)0˚C(32˚F)100˚C(212˚F)150˚C(302˚F)200˚C(392˚F)250˚C(482˚F)Fig. 12: Ambient temperature - Pr
Voltage supplySupply voltage 20 … 253 VAC, 50/60 Hz, 20 … 72 VDC(atU >60 VDC, the ambient temperature can bemax. 50 °C/122 °F)Power consumption 1 …
9.2 DimensionsOPTISWITCH 5100 C, 5150 C112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 2
9 Supplement9.1 Technical data...249.2 Dimensions ...29OPTISWITCH 5100 C, 5150 C - with relay output 3Co
OPTISWITCH 5100 C, 5150 CG3/4A, 3/4"NPTG1A, 1"NPT18,5mm(47/64")32 (G3/4A, 3/4"NPT)41 (G1A, 1"NPT)57mm(2 1/4")50mm(1 31/3
SupplementOPTISWITCH 5100 C, 5150 C - with relay output 3130426-EN-060831
Subject to change without notice30426-EN-060831
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 SIL conformityOPTISWITCH 5100 C, 5150 C fulfills the requirements offunctional safety according to IEC 61508/IEC 61511. You canfind further informat
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 5100 C, 5150 C level sensorl Documentation- this operating instruc
Thanks to its simple and robust measuring system, OPTI-SWITCH 5100 C, 5150 C is virtually unaffected by thechemical and physical properties of the liqu
On the electronics module you will find the following indicatingand adjustment elements:l signal lamp for indication of the switching condition (green/